10 Series Pilot Operated Tank Blanketing Valve
10 Series Pilot Operated Tank Blanketing Valve Protectoseal Series 10, 2” Pilot Operated Tank Blanketing Valve is designed to regulate the flow of a blanketing gas (usually Nitrogen) into the vapor space of a flammable liquids storage tank. The valve senses the pressure in the vapor space and opens fully when the tank pressure equals the valve’s set point to allow a flow of gas into the tank. When tank pressure returns to near the valve’s set point the flow of gas is stopped. Each unit consists of a main valve which controls the flow of inert gas into the tank, and the pilot valve which accurately senses the tank’s pressure and controls the opening and closing of the main valve.

• Pilot operated design provides tight operating band
• Optional flow plugs tailor flow capacity to specific requirements and conserve blanketing gas
• Fully field serviceable minimizing down-time Deka ProsesDatasheet
Sizes : 2″ NPT inlet & outlet standard
Inlet gas pressure range : 40 PSIG to 130 PSIG
Settings : -0.5 in. W.C. to 69.2 in. W.C.
Materials : Metal Parts – 316 Stainless Steel
Soft Goods : FEP, Buna N, Neoprene, Viton®, EPDM, Chemraz®, Kalrez®;
Filter : Aluminum, Stainless Steel
Testing & Certifications : ATEX Directive